bob1029 4 hours ago

> Any energy source can provide power.

Not all prime movers are the same with regard to grid dynamics and their impact.

Solar, wind, etc., almost universally rely on some form of inverter. This implies the need for solid state synthetic inertia to provide frequency response service to the grid.

Nuclear, coal, gas, hydropower, geothermal, etc., rely on synchronous machines to talk to the grid. The frequency response capability is built in and physically ideal.

Both can work, but one is more complicated. There are also factors like fault current handling that HN might think is trivial or to be glossed over, but without the ability to eat 10x+ rated load for a brief duration, faults on the grid cannot be addressed and the entire system would collapse into pointlessness. A tree crashing into a power line should result in the power line and tree being fully vaporized if nothing upstream were present to stop the flow of current. A gigantic mass of spinning metal in a turbine hall can eat this up like it's nothing. Semiconductors on a PCB in someone's shed are a different story.

quickthrowman 4 hours ago | parent | next [-]

Large solar sites are required to be able to provide reactive power as well as maintain a power factor of 0.95 to avoid all of the issues you mentioned.

Reddit post by an EE explaining it better than I can: https://www.reddit.com/r/AskEngineers/comments/qhear9/commen...

> There are also factors like fault current handling that HN might think is trivial or to be glossed over, but without the ability to eat 10x+ rated load for a brief duration, faults on the grid cannot be addressed and the entire system would collapse into pointlessness.

I don’t understand what you are talking about here. I don’t work in the utility world, I sell and run commercial electrical work, but handling available fault current in my world is as simple as calculating it and providing overcurrent protection with a high enough AIC rating or current limiting fuses. I don’t see why the utility side would be any different.

Filligree 3 hours ago | parent | next [-]

The utility side has found that vaporising short circuits is a useful feature, as that includes e.g. twigs hitting a power line.

There are breakers, of course, but they react slowly enough that there will absolutely be a massive overdraw first. Then the breaker will open. Then, some small number of seconds later, it will automatically close.

It will attempt this two to four times before locking out, in case it just needs multiple bursts. It’s called “burning clear”, and it looks just as scary as you’d think… but it does work.

So, solar suppliers need to also survive this.

bob1029 4 hours ago | parent | prev [-]

Reactive power handling concerns are in addition to the issues I described. Not equivalent to them.

quickthrowman 3 hours ago | parent [-]

Gotcha, I think I understand now.

The lack of rotating mass in a solar site means the rest of the spinning mass of the generators needs to compensate to maintain frequency and voltage, right? So when clouds roll in and the solar field output drops quickly, it’s a challenge for the rest of the system to compensate since any other generator that spins will slow down much more slowly, giving the grid more time to react.

Also, I was not aware that inverters can only handle fault current that is 1.1x the nameplate capacity, that’s a big limitation. I can buy a 20A breaker with 200kaic, which is 10,000x higher than the breaker ampacity, which is extremely helpful for handling fault current.

reactordev 3 hours ago | parent [-]

Look into GFM’s and FRT’s. You can arc it away.

ViewTrick1002 3 hours ago | parent | prev | next [-]

Or just grid forming inverters?

https://spectrum.ieee.org/electric-inverter-2667719615

bob1029 an hour ago | parent [-]

These do not address the concern of fault current handling. This is a much more localized and severe condition than frequency deviation. Think about dropping a literal crowbar across the output of a solar inverter. This is a situation the grid has to deal with constantly.

I'd argue that nothing that uses semiconductors would be suitable for the task. They get you to maybe 2x rated current capacity for a meaningful duration. A spinning turbine can easily handle 10x or more for a much longer duration.

We could put so many redundant transistors in parallel that we have equivalent fault handling, but then we are into some strong economic issues. There's also no room for error with semiconductors. Once you start to disintegrate, it's all over ~instantly. There is no way to control this. A synchronous machine can trade downstream maintenance schedule for more current right now. The failure is much more gradual over time. A human operator can respond quickly enough if the machine is big enough.

ViewTrick1002 33 minutes ago | parent [-]

Grid forming inverters provide 1/3 to 1/4 the fault current of a similarly sized generator.

The other trivial solution are synchronous condensers. Or just let the generators and maybe even turbines of future emergency reserve thermal plants spin with the grid without consuming any fuel.

Just ensure the proper margins exist in the grid and call in ancillary services as needed.

No need to make it harder than it needs to be.

https://spectrum.ieee.org/amp/baltic-power-grid-2666201539

reactordev 4 hours ago | parent | prev [-]

Yeah, DC vs AC power. 12v vs 120v or 240v. This isn’t a limitation. All energy sources must be converted to useable energy to the grid somehow. So every power source requires an inverter or a down stepper or a really advanced rectifier or all of the above.

bruckie 2 hours ago | parent [-]

The people you're replying to aren't talking about converting from AC to DC or stepping voltage up or down. Rather, they're talking about grid stability. You can have mechanisms to convert from AC to DC and to step voltage up or down, but still have a unstable grid. We had a notable example of that last year: https://en.wikipedia.org/wiki/2025_Iberian_Peninsula_blackou....

One way to think about this problem is that our electrical grids are giant machines—in many ways, the largest machines that humanity has every constructed. The enormous machine of the grid is comprised of many smaller connected machines, and many of those have spinning loads with enormous mechanical inertia. Some of those spinning machines are generators (prime movers), and some are loads (like large electric motors at industrial facilities). All of those real, physical machines—in addition to other non-inertia generators and loads—are coupled together through the grid.

In the giant machine of the grid, electricity supply and demand have to be almost perfectly in sync, microsecond to microsecond. If they're not, the frequency of the grid changes. Abrupt changes in frequency translate into not only electrical/electronic problems for devices that assume 60 Hz (or 50, depending on where you are), but into physical problems for the machines connected to the grid. If the grid frequency suddenly drops (due to a sudden drop in generation capacity or sudden drop in load), the spinning masses connected to the grid will suddenly be under enormous mechanical stress that can destroy them.

It's obviously not possible to instantaneously increase or decrease explicit generation in response to spikes or drops in load (or alternatively, instantaneously increase or decrease load in response to spikes or drops in generation). But we don't need to: all of the spinning mass connected to the grid acts as a metaphorical (and literal) flywheel that serves as a buffer to smooth out spikes.

As the generation mix on the grid moves away from things with physical inertia (huge spinning turbines) and toward non-inertial sources (like solar), we need to use other mechanisms to ensure that the grid can smoothly absorb spikes. One way to do that is via spinning reserves (e.g. https://www.sysotechnologies.com/spinning-reserves/). Another way to do it is via sophisticated power electronics that mimic inertia (such as grid-forming inverters, which contrast with the much more common grid-following inverters).

To learn more about this topic, look up ancillary services (e.g. https://en.wikipedia.org/wiki/Ancillary_services). This Shift Key podcast episode is also a great introduction: https://podcasts.apple.com/us/podcast/spains-blackout-and-th...

LikeBeans 2 hours ago | parent | next [-]

Great explanation about the grid being a giant machine that couple smaller machines with each other. About your last point, the buffer, I think batteries (chemical and also physical) seems to be the main key going forward.

reactordev 2 hours ago | parent | prev [-]

I actually have a patent in this space for demand response. I know. I was being a bit cheeky. Stability is still a concern as unstable loads and generation needs to be mitigated as well as properly phased.