| ▲ | thyristan an hour ago | |||||||
The problem is, if you feed cold water into your normal heating pipes, all the piping and radiators will get wet from condensation. So you would have to have a regulator that measures air moisture and temperature in all your rooms and only feeds water with a temperature above the dew point. This is possible, but inefficient and (especially on hot+wet days) doesn't cool very well. The possible real fixes are either to section off your water circuits in summer, and only run the properly cold water through FCUs, wall or ceiling loops. Or to get a multisplit heat pump, use a normal refrigerant-air indoor unit to cool and a refrigerant-water indoor unit to heat the water loops. | ||||||||
| ▲ | dom96 an hour ago | parent [-] | |||||||
Yeah, I wasn't planning to run the cold loops through the existing radiator piping. I just want the ability to cool at least 1 room by reusing the air-to-water system, even if that means the FPU requires its own piping from the outside. In that scenario, are FPUs a good option? Are there other drawbacks? | ||||||||
| ||||||||