| ▲ | formerly_proven 4 hours ago | |||||||
The situation in germany is essentially the same, but that's why net supply by these is limited to 800 W. I don't think anything changes w.r.t. earth leakage, why would the presence of the solar supply change anything from the RCD and fault point of views, respectively? | ||||||||
| ▲ | mytailorisrich 4 hours ago | parent [-] | |||||||
Not expert but one difference is that in Germany the standard wiring is radial circuits with 16A MCBs while in the UK it's ring wiring with 32A MCBs. So in the UK we have 2.5mm^2 wires in a ring on a 32A MCBs... Of course a 2.5mm^2 wire is rated ~20A so any issues with the ring (sockets still work since connected from the other branch) can burn the wire before the MCB trips... | ||||||||
| ||||||||