| ▲ | razingeden 8 hours ago | |
yes, this is accurate for US and “works” but it’s against code here. you’ll get mildly shocked by metallic cabinets and fixtures especially if you’re barefoot and become the new shortest path to ground. old construction in the US sometimes did this intentionally (so old, the house didn’t have grounds. Or to “pass” an inspection and sell a place) but if a licensed electrician sees this they have to fix it. I’m dealing with a 75 year old house that’s set up this way, the primary issue this is causing is that a 50amp circuit for their HVACs are taking a shorter path to ground inside the house instead of in the panel. As a result the 50 amp circuit has blown through several of the common 20amp grounds and neutrals and left them with dead light fixtures and outlets because they’re bridged all over the place. If an HVAC or two does this, I’d advise against this for your 3200 watt AI rig. EU, you don’t want to try to energize your ground. They use step down transformers or power supplies capable of taking 115-250 (their systems are 240-250V across the load and neutral lines. Not 120 across the load and neutral like ours.) in the US. you’re talking about energizing your ground plane with 120v and I don’t want to call that safe… but it’s REALLY NOT SAFE to make yourself the shortest path to ground on say. a wet bathroom floor. with 220V-250v. | ||